Analysis of abnormal closing fault of 750 kV AIS earthing switch
DOI:
Author:
Affiliation:
Clc Number:
TM51
Fund Project:
Article
|
Figures
|
Metrics
|
Reference
|
Related
|
Cited by
Abstract:
In order to accurately analyze the earthing switch failure causes in windy weather, through the onsite inspection, action process analysis, material analysis of structural parts and the stress condition analysis, this paper confirms that the failure reason of the abnormal closing of this earthing switch is the loosened bolt caused by the unreasonable size design of the crank arm bolt and the unqualified material. Furthermore, the targeted validation tests and preventive measures are carried out to ensure the safe operation of the equipment.
Reference
Related
Cited by
Get Citation
Cite this article as: LI Na, MA Fei-Yue, NIU Bo, XIANG Zhong-Hua, NI Hui, LIU Bo. Analysis of abnormal closing fault of 750 kV AIS earthing switch [J]. J Sichuan Univ: Nat Sci Ed, 2020, 57: 1131.